DD1010/DD1050/DD2050 Ethernet/Ip Gateway (External)
Details
Serial communicator/gateway
Communicator
- Protocol -- Configurable RS-232/422/485 based produce/consume / query/response ASCII
- Max stations -- 31 (with RS485/422)
- Baud rate -- 1.2-57.6kbit/s
- Physical standards -- RS232/422/485
- Modbus Commands
-- 0x01 Read Coils
-- 0x02 Read Discrete Inputs
-- 0x03 Read Holding Registers
-- 0x04 Read Input Registers
-- 0x05 Write Single Coil
-- 0x06 Write Single Register
-- 0x07 Read Exception Status
-- 0x08 Diagnostics
-- 0x0B Get Comm Event Ctr
-- 0x0C Get Comm Event Log
-- 0x0F Write Multiple Coils
-- 0x10 Write Multiple Register
-- 0x11 Report Slave ID
-- 0x14 Read File Record
-- 0x15 Write File Record
-- 0x16 Mask Write Register
-- 0x17 Read/Write Multiple Registers
-- 0x18 Read FIFO
- DF1 Services
-- 0x01 Integrity Check
-- 0x02 Read Diagnostics
-- 0x03 Read Data
-- 0x04 Write Data
Environmental characteristics
- Reverse voltage protection
- Short circuit protection
- Galvanic isolation on sub-network
- MTTF -- >550000h / Telcordia Issue 2 / Method 1 Case 3 at 30°C
- Installation altitude -- up to 2000m
Immunity and emission for industrial environment
- Electrostatic discharge -- +/-4kV
- Electromagnetic RF fields
-- 10V/m 80MHz-1GHz
-- 3V/m 1.4GHz-2.0GHz
-- 1V/m 2.0GHz-2.7GHz
- Fast Transients -- +/-1kV
- Surge protection -- +/-1kV
- RF conducted interference -- 10V/rms
- Emission (at 10m)
-- 40dB 30MHz-230MHz
-- 47dB 30MHz-1GHz
Design
Serial + EtherNet/IP
6 x LED indicators (fieldbus/sub-network/device status)
Supply voltage (DC)
21.6-26.4Vdc (24Vdc nom.)
Connection type
2 x RJ45 connectors (10/100Mbit/s Ethernet)
1 x 9-pin D-sub female connector (serial RS-232/RS-422/RS-485; sub-network)
1 x 2-poles plug-in connector (power)
1 x RJ11 (4P4C modular) PC connector
Protection functions
reverse voltage protection
short-circuit protection
Communication protocol
Ethernet/IP
RS-232
RS-422
RS-485
Mounting mode
DIN rail (35/7.5 or 35/15) mounting
Speed
100Mbit/s (Ethernet)
Degree of protection
IP20
NEMA 1
Dimensions
H120mm x W27mm x D75mm
Material
Plastic housing (ABS / PC)
Ambient air temperature for operation
0...+55 °C
Ambient air temperature for storage
-40...+85 °C
Current consumption
300mA (24Vdc; max.)
100mA (typical)
Contents
configuration cable RS-232 port
installation sheet
D-SUB with screw terminals for sub-network
Customs Tariff Number
8517620090
Compliant with standard(s)
CE
cULus listed
UL94 V-0
RoHS
EN 50022
UL (file number E203225) -- UL 508
Hazardous Locations CLASS 1; DIVISION 2; GROUPS A/B/C/D; T4 -- ISA 12.12.01
CE (2004/108/EC) -- EN 61000-6-4 / EN 61000-6-2
Galvanic isolation on sub-network -- EN 60950-1
Electrostatic discharge -- EN 61000-4-2
Electromagnetic RF fields -- EN 61000-4-3
Fast Transients -- EN 61000-4-4
Surge protection -- EN 61000-4-5
RF conducted interference -- EN 61000-4-6
Emission -- CISPR 16-2-3
EU - Declaration of Conformity
- EN 61000-6-4(2019) Emission standard for industrial environment
- EN 55016-2-3(2017) (Class A)
- EN 55032(2015) (Class A)
- EN 61000-6-2(2019) Immunity for industrial environment
- EN 61000-4-2(2009)
- EN 61000-4-3(2020)
- EN 61000-4-4(2012)
- EN 61000-4-5(2014) + A1(2018)
- EN 61000-4-6(2014)
UK - Declaration of Conformity
- EN 61000-6-4(2007) + A1(2011) Emission standard for industrial environment
- EN 55016-2-3(2017) (Class A)
- EN 55032(2015) (Class A)
- EN 61000-6-2(2019) Immunity for industrial environment
- EN 61000-4-2(2009)
- EN 61000-4-3(2006) + A1(2008) + A2(2010)
- EN 61000-4-4(2012)
- EN 61000-4-5(2014) + A1(2018)
- EN 61000-4-6(2014)
Benefits
Integrate your serial RS-232/422/485 based industrial devices and equipment to a Ethernet/IP control system without the need for any changes to the device -- Just connect & configure and you're done
The Communicator is a proven and trusted protocol converter gateway that connects non-networked industrial devices and equipment to Ethernet/IP.
The gateway performs an intelligent protocol conversion and presents the serial data to the Master PLC/Controller as easily processed I/O data.
- The Communicator is slim stand-alone gateway designed for IP20 and DIN-rail mounting -- requiring a 24V power supply.
The Communicator is conformance tested to current Ethernet/IP specifications guaranteeing network compatibility.
Convert almost any type of serial protocol
The Communicator is capable of converting almost any type of serial protocol such as Modbus RTU / ASCII / DF1 or any other type of proprietary Query/Response or Produce/Consume protocol.
- Convert almost any RS-232/422/485 Request/Response or Produce/Consume protocol in just a few minutes -- for example Modbus RTU / ASCII / DF1.
- Pre-defined for Modbus RTU to avoid the hassle of scripting and serial Modbus frame building with the 6-step Modbus RTU wizard.
- No hardware or software changes are required for the connected automation device
- Compatible with PLCs from leading manufacturers such as Siemens / Rockwell / Schneider Electric / etc.
- Complete protocol conversion performed by the Communicator with no PLC function blocks required
- Handy Save/Load function means a completed configuration can be re-used for many other installations
- Included "Anybus Configuration Manager" with flexible serial frame building capabilities
- Versions with Dual Port switched Ethernet allows for daisy chaining and eliminates the need for external switches
- Global free technical support and consultancy
Serial features
- No high level programming skills are needed to set up the Anybus Communicator as configuration is accomplished using the included easy to use Windows based ACM (Anybus Configuration Manager)
- Selectable RS-232/422/485 interface
- Pre-defined 6-step Modbus-RTU configuration wizard
- Selectable pre-loaded DF1 commands -- no scripting or serial frame building required
- Ability to configure ASCII or vendor specific protocols (Request/Response or Produce/Consume via a visual frame building interface
- Multi-language support for English / German / Spanish / Italian / French / Polish / Russian / Chinese and Japanese
- Handy Save/Load function allows for a completed configuration to be re-used for many other installations
- Password protection prevents unauthorized upload and download of configurations
- Serial Line Listener and In-built Checksum calculations for diagnostic and troubleshooting
Ethernet/IP interface features
- Ethernet/IP conformance tested by ODVA
- Ethernet/IP Adapter Level 2 and Level 3 I/O Server CIP
- Max. 509bytes Input and 505bytes Output data
- 10/100Mbit operation in full or half-duplex
- Device Level Ring (DLR) functionality available (announce-based ring participant)
- Per-user security framework
- Quality of Service (QoS) available
- TCP/IP settings can be configurable with web-page / Configuration Tool / DHCP or ARP
- Integrated switch allowing for a daisy-chain topology
- Dual RJ-45 ports available simultaneously
Humidity
0-95% relative humidity (RH; non-condensing)